Regular Paper : Detection Technique of Partial Discharge by a Capacitive Probe in Cast-resin Transformers
Kwang Seok Jung, Dae Won Park, Hyeon Kyu Cha, Sang Wook Cha, Gyung Suk Kil
J Korean Inst Electr Electron Mater Eng 2011;24(4):319-324.   Published online April 1, 2011
DOI: https://doi.org/10.4313/JKEM.2011.24.4.319
This paper dealt with a partial discharge (PD) detection method for insulation diagnosis in cast-resin transformers. To detect PD pulse, a planar-capacitive probe was designed and fabricated. The probe has no insulation problem and can be installed on cast-resin transformers even in operation since it does not connect with high voltage conductor. The PD measurement system consists of the capacitive probe, a coupling network of 100 [kHz] low-cutoff frequency, and an amplifier with a gain of 40 [dB] and a frequency bandwidth of 500 [Hz]∼45 [MHz]. A plane-needle and a plane-plane electrode system were fabricated to simulate insulation defects in a cast-resin transformer. Sensitivity of the PD measurement system, which is evaluated by a standard calibrator was 0.35 [mV/pC] for positive and 0.45 [mV/pC] for negative, respectively. The PD detection by the capacitive probe was less sensitive than that by a coupling capacitor according to IEC 60270, but we could analyze the magnitude and the phase distribution of PD pulse.

Citations

Citations to this article as recorded by  
  • Machine Learning-Based Partial Discharge Recognition in Cast-resin transformers Using Phase-Synchronized Partial Discharge Detection Technique
    Gyeong-Yeol Lee, Gyung-Suk Kil
    Journal of Electrical Engineering & Technology.2026; 21(6): 5147.     CrossRef
  • 111 View
  • 0 Download
  • 1 Crossref